Common UPS Battery Issues
Last updated: 10 May 2025
28 Views
Common UPS Battery Issues
1. Grid Corrosion
- Occurs in batteries that have exceeded their designed service life
- Caused by natural chemical reactions that gradually corrode the internal grid
- Lead material flakes off from the battery plates over time
- The corrosion process can be slowed but not stopped
- In compact battery designs, this can lead to internal short circuits
2. Sulphation
- Common in UPS systems with frequent charge/discharge cycles
- Happens when batteries are not fully recharged
- Lead sulphate crystals build up on the plates and in the electrolyte
- Leads to higher internal resistance and slower charging
- Light sulphation may be reversed with a 12-hour high-current charge
- Severe sulphation usually requires battery replacement
3. Short Circuits
- Caused by porous positive plate material separating from the grid
- During discharge, shed material may create unintended contact
- Can result in internal cell short circuits and failure
4. Dry Out (Water Loss)
- Typically caused by overcharging
- Overcharging increases acid concentration in the electrolyte
- Leads to water evaporation and reduced capacity
- Results in separator failure and faster self-discharge
- Accelerates sulphation and overall battery degradation
5. Thermal Runaway
- Triggered by a continuous increase in internal battery temperature
- Generates excess heat, which further increases temperature
- Poor heat dissipation causes external and internal heat buildup
- Can result in battery casing deformation or melting
6. Top Mossing
- Caused by poor alignment of plates or separators during manufacturing
- Reduces contact area between plates and electrolyte
- Leads to crystalline moss formation inside the battery
- May cause self-discharge and soft short circuit failures